AIS FR Pipe Wrap FP 807 is designed to maintain the fire resistance of fire separating walls and floors when these are breached by plastic pipes, conduits or metal pipes with continuous combustible insulation, and may be used in drywalls, masonry or concrete walls and concrete floors.
Each pipe wrap consists of a graphite based reactive intumescent strip, which reacts to heat and closes the opening left by the softening plastic pipe or pipe insulation in a fire. The pipe wrap is installed completely around the pipes or insulation and secured with the self-adhesive tab.
The sealant has undergone tests to BS EN 1366-3 for fire protection joints and the durability class is X intended for use at conditions exposed to weathering.
| Description | Sound Reduction |
|---|---|
| Durability & life | Same as the product it is installed within; AIS FR Board or AIS FR Mortar |
| Installation | Refer to Installation Instructions for AIS FR Board and AIS FR Mortar |
| Conditioning procedure | EN 13238:2010 |
| Expansion ratio | 28:1 |
| Expansion pressure | 55 N |
| Colour | Anthracite |
| Graphite weight/density | 1.3 kg/m² per mm thickness / 1300 kg/m³ |
| Normal expansion time | Less than 10 minutes |
| Minimum expansion temp. | 150 °C |
| Storage | Store in temperatures between 5 °C and 30 °C |